Application of Acrel-6000 Electrical Fire Monitoring System in Canon High-tech Park in Zhuhai

Xu Shuang

Ankerui Electric Co., Ltd. Shanghai Jiading

Abstract The Ankerui residual current electrical fire monitoring system is used to monitor electrical fires in low-voltage distribution systems such as shopping malls, hotels, airports, banks, hospitals and factories through ARCM residual current electrical fire monitoring devices. This article focuses on the implementation of the Acrel-6000 electrical fire monitoring system and its significance through the introduction of the electrical fire monitoring system project of the Canon Hi-tech Division in Zhuhai.

Keywords :fire detector; electrical fire; workshop;

0, foreword

In the past 10 years, the number of electrical fires in China has topped the total number of fire accidents. According to the statistics of the Fire Department of the Ministry of Public Security, there were 159,000 fires in 2007 (not including forests, grasslands, and underground fires in mines, the same below). From the direct cause of fires, electrical fires are the most common. Since then, it has accounted for 28.8% of the total. In 2008, there were 133,000 fires. Electrical causes such as electrical short circuits, overloads, and electrical equipment breakdowns caused 40,000 fires, accounting for 30.1% of the total. The proportion increased by 1.3 percentage points from 2007. The proportion of electrical fire accidents has increased year by year, which is worrying. For the severe electrical fire situation, early forecasting, early warning, and forecasting are the top priorities for firefighting, and eliminating the occurrence of electrical fires at the source has become the focus of attention. The task of preventing and effectively curbing electrical fires is imminent. Relevant state departments have successively formulated or revised relevant standards and specifications and required the installation of electrical fire monitoring and alarm systems in buildings.

Based on the new standard of electrical fire monitoring system (GB14827-2005) and the example of leakage current fire monitoring system of Canon Hi-tech Zone in Zhuhai, this paper introduces the application of Acrel-6000 electrical fire monitoring system in workshops and large public places.

1. Project Introduction

The new construction project of Zhuhai High-tech Zone can be located in Jinding Industrial Park of Zhuhai High-tech Zone, covering an area of ​​183,934 square meters. This project is mainly in the five distribution areas of G1 plant, G2 plant, G3 plant, management ridge and power ridge. Each electricity circuit may be forecasted and monitored due to electrical leakage and leakage due to electrical leakage, accurately monitor electrical circuit faults and abnormal conditions, discover electrical fire fire hazards, and promptly alert personnel to eliminate these hidden dangers. Help companies save labor costs, improve work efficiency, and reduce the probability of fire.

The system detects the leakage current, over-current, and over-temperature signals of each power circuit in the scene, and uses sound and light alarms to accurately alert the staff of the location of line faults and monitor the changes in the fault points. Store various faults and operation test signals, and display the system power status to effectively prevent common electrical fire accidents caused by electrical leakage and ensure the safety of people's lives and property.

2, reference standards

The system complies with the People's Republic of China national standard GB14287.1-2005 "Electrical fire monitoring system - Part 1: Electrical fire monitoring equipment."

3, the basic composition and working principle of the system

3.1 The basic components

According to the national standard GB14287-2005 "Electrical Fire Monitoring System" and related specifications "Design method of electrical fire monitoring system" (provisional regulations), the basic composition of the electrical fire monitoring system should include: electrical fire monitoring equipment, residual current electrical fire monitoring Detectors and temperature-based electrical fire monitoring detectors and other three basic product categories. Among them, the residual current type electric fire monitoring detector consists of a monitoring detector and a residual current transformer. The temperature-type electric fire monitoring detector consists of a monitoring detector and a temperature sensor.

The residual current type electric fire monitoring system adopts a hierarchical distributed structure and is composed of a station control layer, a network communication layer, and a field device layer. The system topology is shown in the following figure: Each electrical fire monitoring probe is connected to the communication server through a shielded twisted pair RS485 interface, using a MODBUS communication protocol bus type connection, and then enters the monitoring host through the Category 5 TCP/TP protocol. As shown below:

1) The field device layer is mainly used for various types of meters and protection devices used for leakage current and temperature signal acquisition and measurement in the connection network, and it is also a necessary basic component element for constructing the monitoring system. Not only shoulder the burden of collecting data, but also the terminal component that executes background control commands.

2) Communication control layer is mainly composed of communication server, interface conversion device and bus network. This layer is the bridge for data information exchange. Different interface conversion devices provide various interfaces such as RS232, RS422, RS485, SPABUS, and Ethernet, flexible networking methods, support for point-to-point communication, fieldbus networks, Ethernet, and other types. The configuration network. The communication server is mainly used to directly transmit various control commands of the host computer to the field instrument and instrument, and is responsible for collecting, classifying, and storing the data information sent back by the field instrument. The interface conversion device is due to the field instrument or other series. There is a difference in the communication interface between the device and the host computer. It is necessary to perform the conversion before data exchange.

3) Management The monitoring and control layer is for managers who monitor the network. This layer directly faces the user. This layer is also the uppermost part of the system, mainly by the electrical fire monitoring system software and necessary hardware equipment such as computers, human-machine interfaces, printers, UPS and so on. The software part has a good human-computer interaction interface. It reads the various data information collected by the front-end machine through the data transmission protocol, and is automatically calculated and processed to reflect the operating status of the site by means of graphics, digital display, and sound. Accept the operation command of the management personnel, send and check the execution status of the operation in real time to ensure the normal operation of the power supply unit.

3.2 Working principle

The basic principle is that when the parameters such as leakage current and temperature in the electrical equipment are abnormal or abrupt, the terminal's probe head (such as residual current transformer, temperature sensor, etc.) uses the electromagnetic field sensing principle and temperature effect to collect the information. , And sent to the monitoring probe, through the amplification, A / D conversion, CPU to change the amplitude of the analysis, judgment, and compared with the alarm set value, once the set value is exceeded, an alarm signal, but also transport In the monitoring equipment, it is further identified and determined by the monitoring equipment. When it is confirmed that a fire may occur, the monitoring host issues a fire alarm signal, turns on the alarm indicator, sounds the alarm, and displays the fire alarm and other information on the LCD. . The on-duty personnel quickly checks and handles the accident scene according to the above information, and sends the alarm information to the centralized console.

3.3 Design, Installation and Cabling Design of Monitoring System

The alarm signals of the electrical fire monitoring equipment and system shall be located in the fire control room or the place where the personnel is on duty. The power supply of the host should be taken from the fire control power supply (AC220V) of the control center. Each monitoring detector uses field power, and the power access point should be at the upper end of the circuit breaker.

1) Installation design of the internal form of distribution cabinet

This project is a new construction project. All the monitoring detectors are installed in the distribution cabinet in the substation, and they are embedded and installed on the panel of the distribution cabinet. The staff can check the leakage and temperature information of each circuit through the panel button. Residual current transformers shall be installed on the three-phase power lines A and B, C and N lines. The PE line shall not pass through the transformer and shall be firmly fixed. The connection between the detector and the transformer shall be shielded wire; the temperature sensor shall be A thermistor, NTC, provides a temperature reference of -10 to 120°C. The thermistor can be connected to an electrical leakage fire monitoring detector via a wire.

2) Installation design of the entire leakage fire monitoring system

Each leakage monitoring detector in the site has a 485 communication interface, and all the detectors on the site must be connected in series by means of a shielded twisted pair. When connecting, note that the number of connections per 485 bus does not exceed 32, and It is suitable for about 20. When installing the wiring, attention should be paid to the separation of strong and weak wires. The recommended wire diameter of the flame-retardant shielded twisted pair cable should be no less than 1.0mm2. The shielded wire shield layer should be well grounded, and each bus end should be increased by about 100 ohms. Matching resistance. Neat wiring, bundled into bundles, threading available flame retardant PVC pipe, metal pipe and metal trunking. After the pipe and slot are worn, the nozzle and slot shall be plugged.

3.4 Product Selection and Introduction

The project is divided into five monitoring areas, namely G1 plant, G2 plant, G3 plant, management ridge and power ridge. The plant G1 has 43 monitoring circuits, the plant G2 has 71 monitoring circuits, the plant G3 has 195 monitoring circuits, the management building has 37 monitoring circuits, and the power building has 30 monitoring circuits. This project is installed at the distribution cabinet site. ARCM100 series residual current monitoring detector and AKH-0.66/L type residual current transformer. The AcrelAcrel-6000/Q500 electrical fire monitoring system for the leakage fire monitoring equipment in the management ridge facilitates the unified management of the enterprise staff.

ARCM100 series electrical fire monitoring detectors are intelligent detector products that comply with GB 14287-2005. The product can be used on a large number of online or stand-alone use (with leakage/overcurrent/temperature detection and alarm functions, and optional features: automatic shutdown of the monitored circuit during an alarm, ie relay output function). It integrates electrical fire monitoring detection, alarm functions and power distribution monitoring functions. It is characterized by high intelligence, complete functions, reliable performance, mini design, beautiful appearance, simple setup, and embedded type installation. It is a crystallization of a refreshing new idea design and is another new contribution to preventing electrical fire accidents.

Electrical fire monitoring detectors (hereinafter referred to as "monitoring detectors") consist of residual current transformers, temperature sensors, and monitoring alarms. When the remaining current transformers in the protected circuit (hereinafter referred to as "transformer") detect the remaining When the current exceeds the preset value of the monitoring alarm or the temperature detected by the temperature sensor exceeds a preset value, the monitoring alarm device will issue an audible and visual alarm signal and a control signal after analysis and confirmation. The monitoring alarm can display the leakage current of the alarm circuit, sensor temperature and so on. When the monitoring alarm has alarm information, start the relay. It can directly display the detection current value and temperature value without occupying a large equipment site, saving the cost of fire-fighting equipment and saving electricity and energy.

AcrelAcrel-6000 series monitoring equipment is the top of the entire electrical fire monitoring system. It can connect multiple ARCM series detectors to form a complete set of electrical fire monitoring system with sound and light alarm function. It also displays alarm loops synchronously and its alarm information. Can save more than 12 months, backup uninterruptible power supply can ensure that the city power loss after continuous operation for more than 4 hours, the monitoring system is divided into wall-mounted, piano desktop and cabinet type 3, effective communication distance up to 1200 meters, multiple devices Equipment or other systems such as alarm and fire linkage systems, power monitoring systems, etc. can exchange data. And this series of monitoring equipment with self-test function, from the hardware, software, communication lines, power supply system in all aspects of self-test, in order to keep abreast of the system product running status, to ensure the reliability of the system operation.

3.5 Software Interface

This set of PC software Acrel-6000 electrical fire system. Mainly has the following function characteristic: The friendly man-machine contact surface, may gather the scene equipment the surplus electric current data and the temperature in real time and the time regularly, and has the warning prompt sound and light warning and so on the function. The customer can set the alarm temperature value and leakage current value according to actual needs. When the alarm fault is removed, it can be reset remotely. The system can record alarm events, dates, alarm values, over-line values, and generate reports.

1) Data Acquisition and Display

The on-site leakage fire monitoring detector uploads the collected data to this interface. The user can modify the name of the circuit, monitoring location, and monitoring area as required. When the actual measured value of the residual current is greater than the alarm setting, the system alarm status indicator will automatically flash, and the status of the alarm unit in the corresponding interface will change in color, facilitating the operator to check and handle the alarm.

2) Fault display

When the monitoring device detects a device fault, the status color of the fault unit on the monitoring main interface is changed, the specific information of the faulty unit is displayed, and a fault alarm sound is issued. Supports manual cancellation of fault alarms.

3) Fault and alarm records

With the event storage function, the alarm can record the time, type, parameter and alarm value of the fault and the alarm. According to the alarm record, the fault reason can be analyzed to provide the basis for eliminating the fault.

4 Conclusion

With the development of smart buildings and the widespread use of electricity, people have become more aware of security awareness. The leakage of buildings and installations in enterprises is an inevitable trend of intelligent construction. The electrical fire system is conducive to discovering hidden dangers and dealing with potential safety hazards in time. It is of great significance to prevent fires from occurring. This system has been able to identify and rectify many hidden dangers since Zhuhai Hi-tech Factory was put into operation, which greatly improved the work efficiency of staff, ensured the steady and orderly conduct of daily work, and ensured the safe production of enterprises. The company’s fire management provides a scientific basis.

references

[1]. Ren Cheng, Zhou Zhongzhong. Principles and Application Guide for Digital Meters for Electric Power Measurement [M]. Beijing. China Electric Power Press, 2007. 4

[2]. Wu Enyuan Zhouzhong Electric Fire Monitoring System Design and Application 2012. 8

About the author: Xu Shuang, female, undergraduate, Ankerui Electric Co., Ltd., the main research direction for the smart grid power distribution, Email: mobile phone QQ